PGR-3100 Powr-Gard Ground Fault Indication System With LEDs, 600 V AC, Panel Mount
- MFR:
- Littelfuse
- MFR #:
- PGR-3100
- UPC:
- 079458177312
- Item #:
- 952482
PGR-3100 Powr-Gard Ground Fault Indication System With LEDs, 600 V AC, Panel Mount
- MFR #:
- PGR-3100
- UPC:
- 079458177312
- Item #:
- 952482
Availability
| Location | Available Qty |
|---|---|
| Available | Available to Order |
The PGR-3100 indicates the presence of voltage on each phase of a three-phase system. The LEDs on the panel illuminate when voltage is present. When a ground-fault occurs, the voltage on the faulted phase reduces to ground potential, causing the LEDs for the faulted phase to dim. On a resistance grounded or ungrounded system the LEDs for the unfaulted phases become brighter. Ungrounded ac systems are required by the National Electrical Code (NECĀ®) Article 250.21(B) and the Canadian Electrical Code Part 1, Section 10-106 (2) to have ground detectors, such as the PGR-3100, installed on the system. External potential transformers (PTs) can be used to step down system voltage, allowing the PGR-3100 to be applied to any system voltage. PTs are not required for system voltages up to 600 Vac.
Manuals and Documentation
| Catalog Number | PGR-3100 |
| Manufacturer | Littelfuse |
| Brand | Littelfuse |
| Country of Origin | Mexico |
| Made in USA | No |
| Special Features | Lamp test button |
| Standard | NEC and CEC Code compliant |
| UPC | 079458177312 |
| GTIN | 00079458177312 |
| Item Type | Protection Relay |