Square D™ Schneider Electric

HJL36030C PowerPact Type HJL 100% Rated Molded Case Circuit Breaker, 600 VAC, 250 VDC, 30 A, 20/25/65/100 kA Interrupt, 3 Poles, Thermal Magnetic Trip

MFR #:
HJL36030C
UPC:
785901823896
Item #:
93187
$3,800.88 each
Product Details

PowerPacT H-Frame circuit breakers are designed to protect electrical systems from damage caused by overloads and short circuits. PowerPacT H-Frame circuit breakers are available with either thermal magnetic or Micrologic electronic trip protection units. This PowerPacT H-Frame circuit breaker provides thermal magnetic circuit protection with a breaking capacity of 25kA at 600VAC. All PowerPacT H-Frame circuit breakers are equipped with dual-break rotating contacts that reduce the amount of peak current during a short circuit fault. All PowerPacT circuit breakers have an integral push-to-trip button in the cover to manually trip the circuit breaker. PowerPacT H circuit breakers are available in 2 and 3-pole unit mount and I-Line constructions. This breaker has lugs on both the line and load sides. This PowerPacT H, 30A, 3 pole, circuit breaker has a breaking capacity of 25kA at 600VAC. This circuit breaker has a continuous current rating of 100%. PowerPacT H circuit breakers comply to UL, CSA, NOM, and IEC standards and are CE marked.

Manuals and Documentation

Features

  • Standard 80% or 100% rating
  • Available in Unit mount, I-line or Drawout constructions
  • A wide range of accessories, auxiliaries, and lug connections available

Specifications

Identifiers

Identifiers
Manufacturer Part Number
HJL36030C
GTIN
00785901823896
Identifiers
UPC
785901823896
EAN
0785901823896

General Information

General Information
Manufacturer
Schneider Electric
Brand
Square Dâ„¢
Country Of Origin
US
General Information
Warranty
18 months
Standards Approvals
RoHS Compliant | UL 489 File No. E10027 | CSA C22.2 No. 5-02 File No. LR40970 | CCC/CE Marked | NMX J-266 | Federal Specification W-C-375B/GEN | IEC 60947-2 | NEMA AB1 | eccn: EAR99 | PROP65: This product can expose you to chemicals including: DINP and DIDP which is known to the State of California to cause Carcinogen and Reproductive harm. For more information go to www.p65warnings.ca.gov
Application
Construction, Commercial Buildings, Oil, Gas, Control Equipment Panels, Marine, Industrial Buildings, Water Wastewater, OEM Commercial, Healthcare Facilities, Data Centers, Educational Campuses and Industrial Markets Applications

Dimensions

Dimensions
Dimensions
4.36 in L x 4.12 in W x 6.4 in H

Technical Information

Technical Information
Actuator Type
Toggle
Amperage Rating
30 A
Connection Type
Line/Load Lug
Frame
J
Frequency Rating
50/60 Hz
Interrupt Rating
20/25/65/100 kA
Mounting Type
Surface
Number Of Poles
3
Technical Information
Phase
3
Temperature Rating
40 deg C
Trip Range
350 to 750 A
Trip Type
Thermal Magnetic
Type
Type HJL 100% Rated
Voltage Rating
600 V AC/250 V DC
Wire Size
14 to 3/0 AWG Al/Cu