Product Details
The 3RU21 thermal overload relays up to 40 A have been designed for inverse time delayed protection of loads with normal starting against excessive temperature rises due to overload or phase failure. An overload or phase failure results in an increase of the motor current beyond the set rated motor current. Via heating elements, this current rise heats up the bimetal strips inside the device which then bend and as a result trigger the auxiliary contacts by means of a tripping mechanism. The auxiliary contacts then switch off the load by means of a contactor. The break time depends on the ratio between the tripping current and current setting Ie and is stored in the form of a long term stable tripping characteristic. The "tripped" status is signaled by means of a switch position indicator. Resetting takes place either manually or automatically after a recovery time has elapsed.
Manuals and Documentation
Features
- Class 10
- 3 A at 24/110/120/125 VAC, 2 A at 230 VAC, 1 A at 400 VAC operating current of auxiliary contacts at AC-15, 2 A at 24 VDC, 0.3 A at 60 VDC, 0.22 A at 110/125 VDC, 0.11 A at 220 VDC operating current of auxiliary contacts at DC-13
- Optimized to the 3RT contactors such that in addition to individual mounting they can mounted directly mounted onto the contactors to save space
- Stop button
- Overload and phase failure protection
- Size S0
- B600/R300 contact
- Switch position indicators
- -50 to 80 deg C environmental condition
- TEST function
- Manual and automatic reset
Specifications
Identifiers
| Manufacturer Part Number |
3RU21264EB0
|
|---|---|
| GTIN |
00662643919370
|
| UPC |
662643919370
|
|---|---|
| EAN |
4011209780989
|
General Information
| Manufacturer |
Siemens
|
|---|---|
| Brand |
Siemens
|
| Country Of Origin |
DE
|
| Standards Approvals |
RoHS Compliant | REACH Article 33 | UL Listed | EAC Approved | ATEX Certified | IECEx Certified | ABS Approved | Bureau Veritas CertifiedLRS Listed | PRS Certified | RINA Certified | RMRS Approved | DNV-GL Approved
|
|---|---|
| Application |
For protection of three phase and single phase AC and DC motors
|
Dimensions
| Dimensions |
85 mm H x 45 mm W x 85 mm D
|
|---|
Technical Information
| Amperage Rating |
27 to 32 A
|
|---|---|
| Coil Voltage |
690 V AC
|
| Contact Form |
1NO-1NC 1 Form A/1 Form B
|
| Contact Rating |
32 A at 690 V AC
|
| Enclosure Type |
IP20
|
| Frequency Rating |
50/60 Hz
|
| Mounting Type |
Contactor
|
|---|---|
| Number Of Poles |
3
|
| Power Rating |
30
|
| Temperature Rating |
-20 to 70 deg C
|
| Terminal Type |
Threaded
|