LRD066 TeSys Bi-Metallic Differential Thermal Overload Relay, 1 to 1.6 A, 1NO-1NC 1 Form A/1 Form B Contact
- MFR #:
- LRD066
- UPC:
- 785901822684
- Item #:
- 544230
LRD066 TeSys Bi-Metallic Differential Thermal Overload Relay, 1 to 1.6 A, 1NO-1NC 1 Form A/1 Form B Contact
- MFR #:
- LRD066
- UPC:
- 785901822684
- Item #:
- 544230
Product Details
TeSys LRD thermal overload relay, 1.6A/690V, thermal setting range 1-1.6A, tripping class 10A, for protection of 3-phase motors 0.55kW@400V. Differential device with phase failure and load unbalance detection. It provides a thermal adjustement dial, a manual-automatic reset selector, a test selector for simulation of a tripping, reset and stop buttons, a flag indicator and 2 auxiliary contacts 1NO+1NC for fault signalling. Settings are protected by a transparent cover lockable by sealing. Connection by screw clamp terminals, it connects directly to the bottom terminals of 3-pole contactors LC1D09-D38. Mounting on DIN rail or screw fixing, separated from the contactor, with use of a terminal block LAD7B106 (to be ordered separately). Multi standards certified (IEC, UL, CSA, CCC, EAC, ATEX, Marine).
Manuals and Documentation
Features
- Tesys Deca thermal overload relays are designed to protect a.c. circuits and motors against overloads
- New modern look and feel of all machines
- Easier to install and operate with multi-standard screws
- Digital customer experience for technical documents
- Maintenance guide via EcoStruxureTM Facility Expert
Specifications
Identifiers
| Manufacturer Part Number |
LRD066
|
|---|---|
| GTIN |
03389110822687
|
| UPC |
785901822684
|
|---|---|
| EAN |
3389110822687
|
General Information
| Manufacturer |
Schneider Electric
|
|---|---|
| Brand |
Schneider Electric
|
| Country Of Origin |
FR
|
| Warranty |
18 months
|
|---|---|
| Standards Approvals |
RoHS Compliant | IEC 60947-4-1 | IEC 60947-5-1 | EN 60947-4-1 | EN 60947-5-1 | ATEX D 94/9/CE | CSA C22.2 No. 14 | UL 508 | BV Certified | CCC Certified | DNV Certified | GL Certified | GoST-R Certified | Lloyd's Register Certified | RINA Certified | Green Premium | REACH Compliant | ECCN: EAR99 | PROP65: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.p65warnings.ca.gov
|
| Application |
For motor protection
|
Dimensions
| Dimensions |
1.77 in W x 2.76 in D
|
|---|
Technical Information
| Amperage Rating |
1 to 1.6 A
|
|---|---|
| Contact Form |
1NO-1NC 1 Form A/1 Form B
|
| Contact Rating |
600 V AC
|
| Enclosure Type |
IP20
|
| Frequency Rating |
0 to 400 Hz
|
| Mounting Type |
DIN Rail/Surface
|
| Number Of Poles |
3
|
|---|---|
| Series |
LRD
|
| Temperature Rating |
-4 to 140 deg F
|
| Terminal Type |
Screw Clamp
|
| Type |
Bi-Metallic Differential
|