Square D™ Schneider Electric

C2M200S 2-Circuit Field Installed Rainproof Combination Service Entrance Meter Main, 120/240 VAC, 200 A, 1 Phase, NEMA 3R Enclosure

MFR #:
C2M200S
UPC:
785901291770
Item #:
49699
$1,386.64 each
Product Details

Square D™ Meter Mains are single phase power distribution panels used in residential applications where local codes require service disconnects to be located outside the dwelling. The meter socket supports a standard utility meter and a main disconnect breaker which provides a time and space saving solution for contractors and installers. Meter mains are surface mount with provisions. This is for the field installation of the service disconnect(s) that feed devices downstream. Interior subfeed load centers are typically used with these. This CSED is a QO ring type, class 320 socket with no bypass, and underground feed. With a current rating of 200A, this product has a short circuit current rating of 22kA. This unit is supplied with a factory installed QOM2-VH main breaker. Main lug interior option is also available. Devices meet the Electric Utility Service Equipment Requirements Committee (EUSERC) standards, Federal Specifications W-P-115C for government housing.

Manuals and Documentation

Features

  • Multiple disconnect units can accommodate plug-on surge breaker™ secondary surge arrester
  • Multiple disconnect units can be converted to semi-flush with addition of flange kit
  • 4 AWG to 250 kcmil aluminum/copper line side, (2) 8 to 2/0 AWG aluminum/copper service ground lug
  • Without bypass

Specifications

Identifiers

Identifiers
Manufacturer Part Number
C2M200S
GTIN
00785901291770
Identifiers
UPC
785901291770
EAN
0785901291770

General Information

General Information
Manufacturer
Schneider Electric
Brand
Square D™
Country Of Origin
MX
General Information
Warranty
18 Months
Standards Approvals
RoHS Compliant | UL 50 | UL 67 | UL 414 File No. E6294 | ANSI C12.7 | NEMA PB-1 | EUSERC Approved | Federal Specification W-P-115C | PROP65: This product can expose you to chemicals including: Diisononyl phthalate (DINP), which is known to the State of California to cause cancer, and Di-isodecyl phthalate (DIDP), which is known to the State of California to cause birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
Application
Residential, Service Equipment and Compact Design Applications

Dimensions

Dimensions
Dimensions
18.23 in H x 19.58 in W x 4.6 in D

Technical Information

Technical Information
Amperage Rating
200 A
Cover Type
Ring
Enclosure Type
NEMA 3R
Feed Type
Overhead/Underground
Hub Size
1/2 in
Hub Type
A
Technical Information
Mounting Type
Surface
Phase
1
Terminal Type
Line/Service Ground Lug
Type
2-Circuit Field Installed Rainproof
Voltage Rating
120/240 V AC
Wire Size
4 AWG to 250 kcmil, 8 to 2/0 AWG Aluminum/Copper