LR3D126 TeSys Bi-Metallic Non-Differential Thermal Overload Relay, 5.5 to 8 A, 1NO-1NC 1 Form A/1 Form B Contact

MFR #:
LR3D126
UPC:
785901851783
Item #:
463318
$132.59 each
Product Details

TeSys LRD thermal overload relay, 8A/690V, thermal setting range 5.5-8A, tripping class 10A, for protection of 3-phase motors 3kW@400V. Non differential device, it can be used with unbalanced loads. It provides a thermal adjustement dial, a manual-automatic reset selector, a test selector for simulation of a tripping, reset and stop buttons, a flag indicator and 2 auxiliary contacts 1NO+1NC for fault signalling. Settings are protected by a transparent cover lockable by sealing. Connection by screw clamp terminals, it connects directly to the bottom terminals of 3-pole contactors LC1D09-D38. Mounting on DIN rail or screw fixing, separated from the contactor, with use of a terminal block LAD7B106 (to be ordered separately). Multi standards certified (IEC, UL, CSA, CCC, EAC).

Manuals and Documentation

Features

  • Tesys Deca thermal overload relays are designed to protect a.c. circuits and motors against overloads
  • Suitable for unbalanced loads
  • New modern look and feel of all machines
  • Easier to install and operate with multi-standard screws
  • Digital customer experience for technical documents
  • Maintenance guide via EcoStruxureTM Facility Expect

Specifications

Identifiers

Identifiers
Manufacturer Part Number
LR3D126
GTIN
03389110378290
Identifiers
UPC
785901851783
EAN
3389110378290

General Information

General Information
Manufacturer
Schneider Electric
Brand
Schneider Electric
Country Of Origin
FR
General Information
Warranty
18 Months
Standards Approvals
RoHS Compliant | IEC 60947-4-1 | IEC 60947-5-1 | EN 60947-4-1 | EN 60947-5-1 | ATEX D 94/9/CE | CSA C22.2 No. 14 | UL 508 | BV Certified | CCC Certified | DNV Certified | GL Certified | GoST-R Certified | Lloyd's Register Certified | RINA Certified | Green Premium | WEEE Compliant | REACH Compliant | ECCN: EAR99 | PROP65: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.p65warnings.ca.gov
Application
For motor protection

Dimensions

Dimensions
Dimensions
1.77 in W x 2.76 in D

Technical Information

Technical Information
Amperage Rating
5.5 to 8 A
Contact Form
1NO-1NC 1 Form A/1 Form B
Contact Rating
600 V AC
Enclosure Type
IP20
Frequency Rating
0 to 400 Hz
Mounting Type
Surface
Technical Information
Number Of Poles
3
Series
LR3D
Temperature Rating
-20 to 60 deg C
Terminal Type
Screw Clamp
Type