TeSys GV electrical trip, MN undervoltage release, 220-240V AC 50Hz, for motor circuit breakers GV2, GV3. It trips the circuit breaker when the control voltage drops below 0.35 Uc, possible opening between 0.35-0.7 Uc. Closing of the circuit breaker is only possible when the control voltage is applied in the range 0.85-1.1 Uc. To be mounted on right-hand side of the circuit breaker, connection by screw clamp terminals. Multi standards certified (IEC, UL, CSA, CCC, EAC).

Manuals and Documentation
Catalog Number GVAU225
Manufacturer Schneider Electric
Brand SCHNEIDER ELECTRIC
Warranty Description Contractual Warranty:18 months
Country of Origin Czech Republic