Product Details
These kits are applicable for indoor and outdoor installations, including direct burial, aerial and submersible applications. Each kit requires at least 1 roll of 3M™ armor cast structural material. For use with 3/C or 4/C armor power cable (Teck-90) up to 1000 V. 3M™ 3/C armored power cable 5730 series accommodates a full range of cable sizes from 14 AWG to 750 kcmil. The overall jacket diameter ranges from 0.62 to 4 (16 to 10 mm). Notes: connectors are not included in the kit. Use only csa certified compression connectors. Vinyl or nylon butt connectors are preferred for 5730 and 5731 series. Amount of armor cast needed is based on two half-lapped layers and 15 ft rolls.
Manuals and Documentation
Features
- Cold shrink in-line splice kit is designed for 600 vac rated armor power cables with aluminum or copper conductors
- The splice kit requires 1 roll of armor Cast™ structural material
- 1/case
Specifications
Identifiers
| Manufacturer Part Number |
5732
|
|---|
General Information
| Manufacturer |
3M
|
|---|---|
| Brand |
3M™
|
| Country Of Origin |
US
|
| Standards Approvals |
CSA Certified
|
|---|---|
| Application |
Aerial, Direct Burial, Indoor/Outdoor, Submersible and 3/C or 4/C Armor Power Cable Applications
|
| Includes |
PST Jacket Tube, (2) Shielding Tape 24 Strips, Copper Shielding Sleeve and (2) Constant Force Springs
|
Technical Information
| Series |
5730
|
|---|---|
| Type |
3-Cable Cold Shrink Low Voltage In-Line
|
| Voltage Rating |
1 kV AC
|
|---|