A4BY2000 Amp-Trap Current Limiting Low Voltage Time Delay Fuse, 2000 A, 600 V AC/300 V DC, 200/100 kA Interrupt, L Class, Cylindrical Body
- MFR #:
- A4BY2000
- UPC:
- 782001939236
- Item #:
- 189604
A4BY2000 Amp-Trap Current Limiting Low Voltage Time Delay Fuse, 2000 A, 600 V AC/300 V DC, 200/100 kA Interrupt, L Class, Cylindrical Body
- MFR #:
- A4BY2000
- UPC:
- 782001939236
- Item #:
- 189604
$6,999.92
each
Product Details
Amp-Trap A4BY fuses have been the industry's favorite when it comes to protecting service entrance equipment, feeder circuits, and circuit breakers. The A4BY is a 100percent rated device and may be applied at continuous currents up to its ampere rating. A 4-second minimum time delay at 500percent rating allows the A4BY to pass normal current surges and to coordinate with ground fault relays.
Manuals and Documentation
Features
- Unique dimensions prevent replacement by other fuse classes
- Blade stamped catalog numbers for permanent identification
- Glass melamine body and-plated terminals provide superior reliability in harsh environments
- Uniform characteristics in all ampere ratings
- Silver-plated copper contact
- North American power fuses
Specifications
Identifiers
| Manufacturer Part Number |
A4BY2000
|
|---|---|
| GTIN |
00782001939236
|
| UPC |
782001939236
|
|---|
General Information
| Manufacturer |
MERSEN
|
|---|---|
| Brand |
Mersen
|
| Country Of Origin |
MX
|
| Standards Approvals |
RoHS Compliant | UL 248-10 | UL File No. E2137 | CSA C22.2 No.248.10 | IEC 269-2-1
|
|---|---|
| Application |
Mains, Feeders, Circuit Breakers, Load Centers, Panelboards, Switchboards and Metering Centers Applications
|
Technical Information
| Amperage Rating |
2000 A
|
|---|---|
| Body Size |
3-1/2 in Dia x 10-3/4 in L
|
| Body Type |
Cylindrical
|
| Class |
L
|
| Element |
Dual
|
| Indicating Non Indicating |
Non-Indicating
|
| Interrupt Rating |
200/100 kA
|
| Material |
Fiber
|
| Mounting Type |
Bolted-On
|
|---|---|
| Rejection Non Rejection |
Rejection
|
| Response Time |
4 s at 500%
|
| Series |
A4BY
|
| Terminal Type |
Blade
|
| Type |
Current Limiting Low Voltage
|
| Voltage Rating |
600 V AC/300 V DC
|