LR2D3561 TeSys LRD Differential Thermal Overload Relay, 55 to 70 A, 1NO-1NC 1 Form A/1 Form B Contac
- MFR #:
- LR2D3561
- UPC:
- 785901317197
- Item #:
- 173240
LR2D3561 TeSys LRD Differential Thermal Overload Relay, 55 to 70 A, 1NO-1NC 1 Form A/1 Form B Contac
- MFR #:
- LR2D3561
- UPC:
- 785901317197
- Item #:
- 173240
Product Details
LR2D3361 is a TeSys LRD thermal overload relay from Schneider Electric to be used with a TeSys D contactor. It protects motors 30-37kW@400V thanks to a thermal range 55-70A, a tripping class 20 and phase unbalance protection. LR2D3361 is a TeSys LRD thermal overload relay from Schneider Electric for direct mounting on TeSys D contactors. With a thermal setting range 55-70A, a tripping class 20 and phase unbalance detection, it protects motors 30-37kW@400V. It provides manual test & reset buttons, automatic reset, trip auxiliary contact and flag indicator. Available worldwide, it is multi-standards certified (IEC, UL, CSA, CCC, EAC, Marine). Thermal overload protection relay, bimetallic type, with phase unbalance protection (differential). Direct mounting on the bottom terminals of a Tesys contactor LC1D80 and D95 to form a compact starter. Light and compact, 70mm wide. Temperature compensated for a good accuracy of the protection. Manual control with test & reset buttons, manual / automatic reset selector. Trip signaling with 1NO+1NC auxiliary contacts and trip flag indicator. Can be completed with terminal blocks for separate mounting (LAD7B, LAD96) and remote control devices (LAD703, LA7D03).
Manuals and Documentation
Features
- New modern look and feel of all machines
- Easier to install and operate with multi-standard screws
- Digital customer experience for technical documents
Specifications
Identifiers
| Manufacturer Part Number |
LR2D3561
|
|---|---|
| GTIN |
03389110229127
|
| UPC |
785901317197
|
|---|---|
| EAN |
3389110229127
|
General Information
| Manufacturer |
Schneider Electric
|
|---|---|
| Brand |
Schneider Electric
|
| Country Of Origin |
US
|
| Warranty |
18 Months
|
|---|---|
| Standards Approvals |
UL 508 | CSA C22.2 | IEC/EN 60947-4-1 | IEC/EN 60947-5-1
|
| Application |
For used to protect AC circuits and motors against overload, phase failure, long starting times and prolonged stalling of the motor
|
Dimensions
| Dimensions |
100 mm H x 75 mm W x 121 mm D
|
|---|
Technical Information
| Amperage Rating |
55 to 70 A
|
|---|---|
| Contact Form |
1NO-1NC 1 Form A/1 Form B
|
| Enclosure Type |
IP20
|
| Frequency Rating |
0 to 400 Hz
|
| Mounting Type |
DIN Rail/Surface
|
| Number Of Poles |
3
|
|---|---|
| Series |
TeSys™ LRD
|
| Temperature Rating |
-20 to 60 deg C
|
| Terminal Type |
Screw Clamp
|
| Type |
Bi-Metallic Differential
|