Square D™ Schneider Electric

500SV82B Dry Sealed Buck and Boost Transformer, 240/480 V AC Primary, 24/48 VAC Secondary, 0.5 kVA Power Rating, 60 Hz, 1 Phase

MFR #:
500SV82B
UPC:
785901709091
Item #:
155601
$1,238.24 each
Product Details

A Buck & Boost Transformer is an insulating transformer with either a 120 V x 240 V primary with a 12/24 V or 16/32 V secondary, or a 240 V x 480 V primary with a 24/48 V secondary. A Buck & Boost Transformer is also useful in applications where the primary and secondary are interconnected for use as an autotransformer. The equipment enclosure is designed and constructed for indoor or outdoor use and is NEMA 3R rated. Square D Buck and Boost Transformers are UL and cUL listed. This Buck and Boost Transformer is a 1 phase, and has a NEMA 3R enclosure rating. This transformer has a primary voltage of 240 x 480 V and a secondary voltage of 24/48 V. This product have a temperature rise of 80 °C. Dimensions for this product are 157 mm (H), 157 mm (W), 115 mm(D), and a weight of 13.8 lb(US).

Manuals and Documentation

Features

  • Dual primary and Dual secondary isolation transformers, allowing for 12 field connected auto-transformer connections for 5%, 6.6%, 10%, 13.3% 20% or 26.6% change in voltage for 1 or 3-phase configurations
  • Unique enclosures for each kVA size - giving the most compact units in the market and not supplying greater than 3 kVA when the cable sizes start to exceed the wiring compartment for isolation transformers sizing
  • Resin filled transformers
  • Painted steel enclosure

Specifications

Identifiers

Identifiers
Manufacturer Part Number
500SV82B
GTIN
00785901709091
Identifiers
UPC
785901709091
EAN
0785901709091

General Information

General Information
Manufacturer
Schneider Electric
Brand
Square D™
Country Of Origin
US
General Information
Warranty
18 Months
Standards Approvals
ANSI Z535.3 | ECCN EAR99 | CSA C22.2 no.66-1988 | cUL/UL 506 | REACH Compliant | RoHS Compliant | PROP65: This product can expose you to chemicals including: Phenyl glycidyl ether, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.p65warnings.ca.gov
Application
For buck and boost primary use is that the primary and secondary can be interconnected for use as an autotransformer

Dimensions

Dimensions
Dimensions
6.19 in H x 6.19 in W x 4.69 in D

Technical Information

Technical Information
Enclosure Type
NEMA 3R
Frequency Rating
60 Hz
Housing Material
Steel
Insulation
130 deg C
Mounting Type
Wall
Phase
1
Technical Information
Power Rating
0.5
Primary Voltage
240/480 V AC
Secondary Voltage
24/48 V AC
Temperature Rating
80 deg C
Type
Dry Sealed