Product Details

TeSys GV motor circuit breaker, 3 poles (3P), 14A/690V, for 3-phase motor applications 5.5kW@400V. It provides a magnetic protection with a tripping level at 13xIn, high breaking capacity Icu 15kA@400V. Connection by screw clamp terminals. Start-stop control by toggle guaranteed for 100 000 cycles AC-3. To complete motor protection, use in association with a thermal overload relay LRD16 (to be ordered separately). Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine).

Manuals and Documentation

Features

  • New modern look and feel of all machines
  • Wide range of GVs - Magnetic, thermal magnetic, different sizes (GV2,GV3,GV4)
  • Easier to install and operate with multi-standard screws
  • Sturdy and long-lasting power connection with EverLink terminals
  • Digital customer experience for technical documents
  • Maintenance guide via EcoStruxureTM Facility Expect

Specifications

Identifiers

Identifiers
Manufacturer Part Number
GV2LE16
GTIN
03389110516999
Identifiers
UPC
785901288626
EAN
3389110516999

General Information

General Information
Manufacturer
Schneider Electric
Brand
Schneider Electric
Country Of Origin
MX
General Information
Warranty
18 months
Standards Approvals
RoHS Compliant | VDE 0113 | EN 60204 | IEC 60947-1 | IEC 60947-2 | VDE 0660 | NFC 63-120 | NFC 63-650 | NFC 79-130 | CSA Certified | CCC Certified | TH Approved | REACH Compliant | WEEE Compliant | Green Premium | ECCN: EAR99 | PROP65: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.p65warnings.ca.gov
Application
Food and Beverage, Material Working, Material Handling, Small Pumps and Packaging

Dimensions

Dimensions
Dimensions
3.5 in H x 1.77 in W x 3.09 in D

Technical Information

Technical Information
Amperage Rating
14 A
Connection Type
Screw Clamp
Control Type
Toggle Switch
Frequency Rating
50/60 Hz
Motor Power
5.5/7.5/9/11 kW
Number Of Poles
3
Operating Cycles
100000 Cycles
Technical Information
Operating Temperature
-20 to 60 deg C
Overload Relay
Class 10 Ambient Compensated
Phase
3
Reset Type
Manual
Series
TeSys™ GV2LE
Type
Circuit Breaker Magnetic
Voltage Rating
690 V AC