LAL36350MB I-Line PowerPact Type LAL Molded Case Circuit Breaker, 600 V AC/250 V DC, 350 A, 10/22/30/42 kA Interrupt, 3 Poles, Thermal Magnetic Trip
- MFR #:
- LAL36350MB
- UPC:
- 785901005520
- Item #:
- 152097
LAL36350MB I-Line PowerPact Type LAL Molded Case Circuit Breaker, 600 V AC/250 V DC, 350 A, 10/22/30/42 kA Interrupt, 3 Poles, Thermal Magnetic Trip
- MFR #:
- LAL36350MB
- UPC:
- 785901005520
- Item #:
- 152097
Product Details
Square D LA molded case circuit breakers provide thermal magnetic protection. Their primary function is automatic opening of a circuit under overload or short circuit conditions or manual opening. LA circuit breakers contain thermal (overload) and magnetic (short circuit) sensing elements in each pole. Push-to-Trip allows the circuit breaker to be manually tripped without exposure to live parts. This Square D LA molded case circuit breaker is a 3 pole unit mount breaker, 350A and 600VAC, with lugs. The thermal magnetic circuit breaker has an interrupting rating of 22kA for 600VAC and 10kA for 250VDC. The circuit breaker MB suffix indicates a shorter handle so that a panel door can close. LA breakers are UL 489, CSA, IEC certified.
Manuals and Documentation
Features
- Use manual circuit open or automatic current interruption for overload or short circuit conditions
- Flexible platform for various types of mounting and terminations
- Unit mount and I-Line construction available
- Short operating handle is factory installed option for this breaker
Specifications
Identifiers
| Manufacturer Part Number |
LAL36350MB
|
|---|---|
| GTIN |
00785901005520
|
| UPC |
785901005520
|
|---|---|
| EAN |
0785901005520
|
General Information
| Manufacturer |
Schneider Electric
|
|---|---|
| Brand |
Square D™
|
| Country Of Origin |
MX
|
| Warranty |
18 months
|
|---|---|
| Standards Approvals |
RoHS Compliant | UL 489 File No. E10027 | CSA C22.2 No. 5-02 File No. LR40970 | CCC/CE Marked | NMX J-266 | Federal Specification W-C-375B/GEN | IEC 60947-2 | NEMA AB1 | PROP65: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.p65Warnings.ca.gov
|
| Application |
For I-Line™ panelboards and switchboards
|
Dimensions
| Dimensions |
5.84 in L x 6 in W x 11 in H
|
|---|
Technical Information
| Actuator Type |
Short Lever
|
|---|---|
| Amperage Rating |
350 A
|
| Connection Type |
Line/Load Lug
|
| Frame |
L
|
| Frequency Rating |
50/60 Hz
|
| Interrupt Rating |
10/22/30/42 kA
|
| Mounting Type |
Unit
|
| Number Of Poles |
3
|
| Phase |
3
|
|---|---|
| Temperature Rating |
-13 to 158 deg F
|
| Trip Range |
1750 to 3500 A
|
| Trip Type |
Thermal Magnetic
|
| Type |
Type LAL
|
| Voltage Rating |
600 V AC/250 V DC
|
| Wire Size |
1 AWG to 600 kcmil, 1 AWG to 250 kcmil Al/Cu
|