Product Details

Eaton’s CH 3/4-inch loadcenters enclose CH circuit breakers for power distribution and circuit protection in residential and light commercial applications. Also called a breaker box, electrical box or even a fuse box, the main function is to take electricity supplied by the utility and distribute it throughout the home to feed lights and receptacles. Covers are typically packaged separately and available as surface or flush mount.

Manuals and Documentation

Features

  • Loadcenters have silver flash plated copper bus in all interiors
  • Boxes and trims are finished using an electrostatic powder coated, baked urethane paint process
  • Steel backpan provides positive, reliable mounting
  • CH 150 to 225 a main breakers are rated 25 kA providing contractors with the highest interrupting rating main breaker in the industry
  • Unique sandalwood finish provides an esthetically appealing, scratch resistant powder coating
  • New mechanical flag feature on CH breakers for easy trip indication
  • Type CH breakers include an industry exclusive "trip to Off" feature that allows a homeowner to easily identify a tripped circuit breaker
  • Copper bus
  • Overhead/underground feed applications

Specifications

Identifiers

Identifiers
Manufacturer Part Number
CH30L3150D
GTIN
00782113097909
Identifiers
UPC
782113097909

General Information

General Information
Manufacturer
Eaton
Brand
EATON
Country Of Origin
US
General Information
Warranty
Limited Lifetime
Standards Approvals
UL 67,UL 50
Application
Electrical Assemblies, Panels and EOEM and Power Distribution Applications

Dimensions

Dimensions
Dimensions
29.13 in L x 14.31 in W x 3.88 in H

Technical Information

Technical Information
Amperage Rating
150 A
Breaker Type
CH
Enclosure Box Size
NEMA D
Enclosure Type
NEMA 1
Housing Material
Metal
Interrupt Rating
10 kA
Mounting Type
Flush
Technical Information
Number Of Circuits
30
Number Of Poles
30
Number Of Spaces
30
Type
3-Phase Standard
Voltage Rating
208Y/120/240 V AC
Wire Size
4 AWG to 300 kcmil
Wiring Configuration
4-Wire