NF418L1C I-Line NF Series 3-Phase Bottom Panelboard Interior, 480Y/277 VAC, 600Y/347 VAC, 125 A, 18 Spaces, 100 kA SCCR
- MFR #:
- NF418L1C
- UPC:
- 785901871293
- Item #:
- 131343
NF418L1C I-Line NF Series 3-Phase Bottom Panelboard Interior, 480Y/277 VAC, 600Y/347 VAC, 125 A, 18 Spaces, 100 kA SCCR
- MFR #:
- NF418L1C
- UPC:
- 785901871293
- Item #:
- 131343
Product Details
NF Panelboard interiors may be used in a wide variety of applications including: commercial buildings; industrial buildings; data centers; stadiums; and offices. NF Panelboards are versatile panelboards that feature a wide selection of bolt-on branch circuit breakers, integral main circuit breakers, bus mounted SPDs, and a wide variety of ready to install accessory kits. NF Panelboard interiors are field convertible to support top or bottom feed. This main lugs interior is rated 125A for 600Y/347VAC, has a plated copper bus, and 18 pole spaces. NF Panelboards are convertible from main lugs to main circuit breaker. NF Panelboards offer 200% rated neutrals for nonlinear loads. Factory installed options include phenolic nameplates, power monitoring of mains and branch circuits, split bus interiors, and neutral assemblies which support up to 36 100A branch circuit breakers. NF Panelboards are available with IP2X per IEC 60529 barriers for UL service entrance applications. Interior has an interrupt current rating of up to 65kA (depending upon the circuit breakers installed). This NF panelboard interior is UL listed for applications in the USA and Canada. Interior accepts ECB, EDB, EGB, and EJB bolt-on branch circuit breakers. Standard mechanical main lug connections will accept copper or aluminum wire. Kits available to replace standard main mechanical lugs with compression lugs, sub-feed lugs, or a vertically mounted main circuit breaker. NF Panelboard interiors are available with plated aluminum or copper bus. Standard 100% rated neutrals accept aluminum and copper wire; field installable kits support 200% rated or copper neutral assembly requirements. NF Panelboards may be used in voltage systems up to 600Y/347VAC.
Manuals and Documentation
Features
- Interior for NF Panelboards
- 125A main lugs with copper bus
- Voltage ratings of 600Y/347VAC max
- Interiors are field convertible to top or bottom feed
- Modular construction accepts field installable accessories
Specifications
Identifiers
| Manufacturer Part Number |
NF418L1C
|
|---|---|
| GTIN |
00785901871293
|
| UPC |
785901871293
|
|---|---|
| EAN |
0785901871293
|
General Information
| Manufacturer |
Schneider Electric
|
|---|---|
| Brand |
Square Dâ„¢
|
| Country Of Origin |
US
|
| Warranty |
18 months
|
|---|---|
| Standards Approvals |
RoHS Compliant | UL 67 | PROP65: Cancer and Reproductive harm - www.P65Warnings.ca.gov
|
Dimensions
| Dimensions |
20 in W x 5-3/4 in D x 27 in H
|
|---|
Technical Information
| Amperage Rating |
125 A
|
|---|---|
| Breaker Type |
EDB/LAL/LHL
|
| Bus Material |
Copper
|
| Enclosure Type |
NEMA 1/3R/5/12
|
| Housing Material |
Aluminum
|
| Mounting Type |
Panel
|
| Number Of Spaces |
18
|
|---|---|
| Series |
NF Series
|
| Short Circuit Current Rating |
100 kA
|
| Type |
3-Phase Bottom
|
| Voltage Rating |
480Y to 277/600Y to 347 V AC
|
| Wiring Configuration |
4-Wire
|