LRD08L6 TeSys Differential Thermal Overload Relay, 2.5 to 4 A, 1NO-1NC 1 Form A/1 Form B Contact, 690 V AC V Coil

MFR #:
LRD08L6
UPC:
785901928607
Item #:
1294709
$155.09 each
Product Details

TeSys LRD thermal overload relay, 4A/690V, thermal setting range 2.5-4A, tripping class 20, for protection of 3-phase motors 1.1-1.5kW@400V. Differential device with phase failure and load unbalance detection. It provides a thermal adjustement dial, a manual-automatic reset selector, a test selector for simulation of a tripping, reset and stop buttons, a flag indicator and 2 auxiliary contacts 1NO+1NC for fault signalling. Settings are protected by a transparent cover lockable by sealing. Connection by screw clamp terminals, it connects directly to the bottom terminals of 3-pole contactors LC1D09-D38. Mounting on DIN rail or screw fixing, separated from the contactor, with use of a terminal block LAD7B205 (to be ordered separately). Multi standards certified (IEC, UL, CSA, CCC, EAC, ATEX, Marine).

Manuals and Documentation

Features

  • Tesys Deca thermal overload relays are designed to protect a.c. circuits and motors against overloads
  • New modern look and feel of all machines
  • Easier to install and operate with multi-standard screws
  • Digital customer experience for technical documents
  • Maintenance guide via EcoStruxureTM Facility Expert

Specifications

Identifiers

Identifiers
Manufacturer Part Number
LRD08L6
GTIN
03606480609800
Identifiers
UPC
785901928607
EAN
3606480609800

General Information

General Information
Manufacturer
Schneider Electric
Brand
Schneider Electric
Country Of Origin
TH
General Information
Warranty
18 months
Standards Approvals
CSA Certified | ATEX Certified | ABS Certified | UL Listed | EAC Certified | EN 60947-5-1 | ATEX D 94/9 | CE Certified | IEC 60947-5-1 | UL File No. 508IEC 60947-4-1 | CSA C22.2 14 | EN 60947-4-1 | IEC 60529 | RoHS Compliant | REACH Compliant | WEEE Certified | PROP65: This product can expose you to chemicals including, Antimony oxide and Antimony trioxide which is known to the State of California to cause Carcinogen harm. For more information go to www.P65warnings.ca.gov.
Application
Standard Motor Protection, Line Protection, Motor Overload, Stalling and Loss of Phase Applications

Dimensions

Dimensions
Dimensions
1.77 in W x 2.99 in W x 2.6 in H

Technical Information

Technical Information
Amperage Rating
2.5 to 4 A
Coil Voltage
690 V AC
Contact Form
1NO-1NC 1 Form A/1 Form B
Enclosure Type
IP20
Frequency Rating
0 to 400 Hz
Mounting Type
DIN Rail/Surface
Technical Information
Number Of Poles
3
Series
TeSys™ LRD
Temperature Rating
-4 to 140 deg F
Terminal Type
Ring Lug/Screw Clamp
Type
Differential Thermal