SE-325 Neutral-Grounding-Resistor Monitor, 120 V AC, 0.5/4 A, NO Contact

MFR:
Littelfuse
MFR #:
SE-325
UPC:
079458988079
Item #:
1280879

Availability

Location Available Qty
Available Available to Order
$6,498.65 each

The SE-325 Neutral-Grounding-Resistor Monitor is used on resistance-grounded systems up to 25 kV to monitor the integrity of the neutral-to-ground path and to detect ground faults. It measures current and voltage in a transformer or generator neutral-to-ground connection and continuity of the neutral-grounding resistor (NGR). The SE-325 coordinates these three measurements to detect a loose connection, corrosion, ground fault, or NGR failure, and provides one alarm or trip output contact.

Manuals and Documentation
Catalog Number SE-325
Manufacturer Littelfuse
Brand Littelfuse
Country of Origin Mexico
Made in USA No
Application Mining
Special Features Continuous NGR monitoring
UPC 079458988079
GTIN 00079458988079
Item Type Trailing Cable Protection