Edison Eaton

ECNR600 ECNR Current Limiting Time Delay Fuse, 600 A, 250 V AC/125 V DC, 200 kAIC Interrupt, Class: RK5, Cylindrical Body

MFR #:
ECNR600
UPC:
782634507567
Item #:
125477
Product Details

Edison's UL Class RK5 dual-element, time-delay fuses provide economical solutions to overcurrent protectioni. Available in both 250Vac and 600Vac, with 200kA RMS Sym interrupting ratings and sizes ranging from 0 to 600 amp.

Manuals and Documentation

Features

  • Provides motor overload, ground fault and short circuit protection
  • Helps protect motors against burnout from overloads and 1 ph when sized properly
  • Simplifies and improves blackout prevention (selective co-ordination ratios)
  • Dual element fuses can be applied in circuits subject to temporary motor overloads and surge currents to provide both high performance short circuit and overload protection
  • The overload element provides protection against low level overcurrent of overloads and will hold an overload which is 5X greater than the amperage rating of the fuse for a minimum of 10 s
  • Superior overload and cycling capabilities
  • True dual element construction allows sizing of 125% FLA for motor backup protection
  • Current limiting provides component short circuit protection
  • For all general purpose applications including lighting, heating and other non-inductive loads
  • Tin plated copper brass terminal and zinc plated steel screws

Specifications

Identifiers

Identifiers
Manufacturer Part Number
ECNR600
GTIN
00782634507567
Identifiers
UPC
782634507567

General Information

General Information
Manufacturer
Eaton
Brand
Edison
Country Of Origin
MX
General Information
Standards Approvals
CE Certified | CSA C22.2 File No.700489/248.12 | UL 248-12 File No.E162363 Guide JDDZ
Application
Industrial Facilities and Factories, Safety and Security Systems, AC Power Distribution System Mains, Feeders, Branch Circuits, Motor, Motor Branch Circuits, Transformers and Other Inductive Loads Applications

Technical Information

Technical Information
Amperage Rating
600 A
Body Size
2.88 in Dia x 10.38 in L
Body Type
Cylindrical
Class
RK5
Element
Dual
Indicating Non Indicating
Non-Indicating
Interrupt Rating
200 kAIC
Technical Information
Material
Fiberglass
Rejection Non Rejection
Rejection
Response Time
10 s at 500%
Series
ECNR
Terminal Type
Blade End
Type
Current Limiting Time Delay
Voltage Rating
250 V AC/125 V DC